The Importance of Measuring Touch and Step Voltages in Practice
Earthing as a safety system
Earthing systems are one of the fundamental pillars of electrical equipment safety. Their main task is to ensure that no dangerous potential differences endangering people and equipment arise under fault conditions. When earth fault currents flow, the potential field around the earthing becomes distorted, giving rise to touch and step voltages. Precisely these quantities are decisive for operator safety.
The standard STN EN 50522:2023 defines the framework for the design and verification of earthing systems in installations above 1 kV. It addresses not only the earthing resistance value itself but, above all, the consequences of fault conditions for people. In practice, this means that even an earthing system with a seemingly satisfactory resistance may prove unsatisfactory in terms of touch voltage. Measurements are therefore not treated as a formality, but as a real verification of the safety function of the entire system.
At EIC, we carry out these measurements as part of the expert assessment of the safety of electrical equipment, focusing not only on the measured values themselves but also on their correct interpretation in the context of the specific installation, local conditions and the requirements of applicable legislation and technical standards.
What we actually measure, and why it cannot be oversimplified
Touch voltage is the potential difference between a conductive part of the equipment and the spot where a person stands. In the event of a fault, current may pass through the body, typically between hand and feet. Step voltage arises between two points on the ground surface, the risk being current passing between the feet and lower body. Both situations depend on the potential distribution in the terrain, which is influenced by the geometry of the earthing as well as the properties of the soil.
Measuring the earthing impedance completes this picture with information on how the earthing system behaves when fault current passes through it. This involves not just the resistive component but the complex impedance, which determines the magnitude of the earth potential rise. A higher impedance generally means a higher earthing potential during a fault, and therefore higher touch and step voltages in its vicinity.
The measurements are evaluated by comparing the measured values with the permissible limits defined by the standard. These limits are not fixed; they depend above all on the duration of the fault. A shorter disconnection time allows higher permissible voltages, whereas for longer exposure the limits become considerably stricter. The assessment also considers factors such as the surface layer or ambient conditions, which affect the resistance of the human body.
When measurement is not a mere formality
Unsatisfactory measurement results represent a serious problem that must not be underestimated. First and foremost, they mean a direct threat to the health and lives of persons, since exceeding the permissible voltage values can lead to heart fibrillation or other fatal consequences. Excessive stress on insulation and secondary faults on electrical equipment may also occur. From an operational perspective, immediate measures are required, often involving reconstruction of the earthing system.
The specifics of electrical substations
Electrical substations form a category of their own: high short-circuit powers are concentrated there, and very large short-circuit currents can flow during a fault. During an earth fault, the earthing potential increases significantly, manifesting itself as an earth potential rise. This phenomenon creates dangerous voltage gradients not only within the substation itself, but also in its immediate surroundings, including fencing and access routes.
Measurements at electrical substations are therefore specific and require increased attention. Large and extensive earthing systems are often interconnected with other metal structures, which complicates the impedance measurement. When measuring touch and step voltages, choosing the right measurement locations is decisive.
Substation measurements are among the activities that EIC performs with an emphasis on expert assessment, the correct measurement methodology and the subsequent technical evaluation of the results. With equipment of this kind, it is crucial not only to measure the values, but also to determine correctly what they mean for operator safety and the reliability of operation.
Operation and the highest-risk moments
Increased risk arises above all during reconstructions and repairs, when work is carried out on the earthing system. Temporarily disconnecting parts of the earthing or changing the current paths can significantly affect the potential distribution. At the same time, personnel move around an environment that is no longer in its original state, which increases the likelihood of contact with dangerous voltages. Particularly critical are situations where the surface layer has been disturbed, for example by removing gravel.
Where the results are unsatisfactory, both technical and organisational measures must be taken. Technical solutions consist mainly of densifying the earthing grid or adding further earth electrodes, thereby reducing the potential gradient. Modifying the surface, for example by applying a layer with a higher resistance, also plays a significant role. Organisational measures include restricting access, adjusting working procedures and thorough training of operating personnel.
Conclusion
Measuring touch and step voltages, together with earthing impedance measurement, is a fundamental tool for verifying the safety of electrical equipment. At electrical substations, it is not merely about meeting the standard’s requirements, but about genuinely managing the risk arising from the physical phenomena that occur during faults. The correct interpretation of the measurements and their thorough evaluation are therefore key to safe and reliable operation.
At EIC, we treat these measurements as a practical tool for verifying the condition of equipment under real operating conditions. Our aim is not only to confirm compliance with the standard, but above all to give the operator clear information on whether the earthing system will actually perform its safety function in the event of a fault.
A measurement report may contain the right numbers, but that does not in itself mean the equipment is safe. What matters is what happens at the moment of a fault. And that is exactly what these measurements should answer.