Active lightning conductors: design and putting into service after the withdrawal of STN 34 1398:2014

In response to ongoing discussions and speculations among the professional community seeking to clarify whether it is currently possible to put into service an active lightning conductor installed in accordance with the Slovak technical standard STN 34 1398:2014, which was withdrawn without replacement, or with another national standard, we have decided to publish our position on the matter.

Introduction

Lightning protection is currently designed and installed in accordance with the valid standards:

  • STN EN 62 305-1 – Part 1: General principles
  • STN EN 62 305-2 – Part 2: Risk management
  • STN EN 62 305-3 – Part 3: Physical damage to structures and life hazard
  • STN EN 62 305-4 – Part 4: Electrical and electronic systems within structures

The standards which set out the requirements for active lightning conductors have been withdrawn without replacement:

  • STN 34 1391:1998 Lightning protection – active lightning conductors, valid from 19 June 1998 to 1 March 2014
  • STN 34 1398:2014 Protection against the effects of lightning – active lightning conductors, valid from 1 March 2014 to 1 March 2017 –withdrawn without replacement

Operation of active lightning conductors put into service before 1 March 2017

Where a lightning protection installation was constructed and put into service while STN 34 1398:2014 was still valid, an electrical equipment inspector may continue to verify the safety of the active lightning conductor by an expert inspection and expert test under that STN. If the lightning protection installation on the building concerned complies with this standard, it may remain in operation. If, based on the findings of inspection activities under Section 9 of Act No. 124/2006 Coll., the lightning protection installation does not meet the safety requirements, the employer is obliged to remedy, in the interests of ensuring occupational health and safety, the shortcomings identified by the inspection activities and, in order to minimise the risks, to plan its reconstruction. In the interests of ensuring occupational health and safety, the employer is obliged to eliminate danger and hazards and, where this is not possible in the light of current scientific and technical knowledge, to take measures to limit them and to prepare measures for their elimination (Section 6(1)(f) of Act No. 124/2006 Coll.).

Putting into service active lightning conductors whose design documentation was prepared and approved before 1 March 2017

If the design documentation of an active lightning conductor was prepared and approved before the withdrawal of standard STN 34 1398:2014 pursuant to Section 14(1)(d) of Act No. 124/2006 Coll., or in the case of all active lightning conductors still under construction classified as classified technical equipment – electrical, group A, whose technical documentation was assessed and an Expert Opinion on the documentation was issued pursuant to Section 5 of Decree No. 508/2009 Coll. by 1 March 2017, they may be completed in accordance with the approved documentation. Before these installations are put into service, the official test and the expert inspection and expert test are carried out in accordance with the standard approved in the design documentation and according to which the equipment was installed, i.e. STN 34 1398:2014. During the final approval (kolaudácia) of the building and its alterations, the Labour Inspectorate will regard this as fulfilment of the requirements for ensuring occupational health and safety.

Protection of buildings against the effects of atmospheric electricity from 1 March 2017

Protection of buildings against the effects of atmospheric electricity is demonstrated by meeting the requirements set out in the STN EN 62 305-1 to 4 series of standards.

Pursuant to Section 38(1) of Act No. 124/2006 Coll., if an employer, or a natural person who is an entrepreneur but not an employer, fulfils the obligations laid down by this Act and by other generally binding legislation on ensuring occupational health and safety in a manner or by a procedure set out in a Slovak technical standard, such fulfilment is regarded as meeting the requirements for ensuring occupational health and safety; these obligations may also be fulfilled in another demonstrably adequate manner.

It follows from the above that an employer, or a natural person who is an entrepreneur but not an employer, may also meet the lightning protection requirements in another way, provided compliance with safety requirements is demonstrated and those requirements do not raise the level of risk of the technical equipment above the level of risk defined in the technical standard.

Certificates, attestations, opinions and similar documents issued before 1 March 2017 confirming the conformity of active lightning conductors with STN 34 1398:2014 Protection against the effects of lightning – active lightning conductors remain valid.

A lightning protection installation (active lightning conductor) on a building constructed and put into service in accordance with regulations and technical standards that are no longer valid (STN 34 1391:1998, STN 34 1398:2014) may remain in operation until its next reconstruction, provided that it complies with those regulations and technical standards – a transitional period applies. If the relevant requirements are not met, the lightning protection installation must be brought into line with the requirements of the valid STN EN 62305 series of standards.

All active lightning conductors still under construction classified as classified technical equipment – electrical, group A, whose technical documentation was assessed and an Expert Opinion on the documentation was issued pursuant to Section 5 of Decree No. 508/2009 Coll. by 1 March 2017, may be completed in accordance with the assessed documentation.

Assessment of the design documentation of active lightning conductors after 1 March 2017

Design documentation submitted for assessment after 1 March 2017 in which lightning protection is designed in accordance with the now invalid standard STN 34 1398:2014, or with a national standard adopted by a foreign national standardisation body which does not meet the minimum requirements set out in the valid lightning protection standards, will be assessed by our company as non-compliant with the valid legislation and other regulations on ensuring occupational health and safety.

Official tests and other tests of active lightning conductors after 1 March 2017

Where an official test or other test is carried out before putting into service an active lightning conductor whose design documentation was prepared and assessed after 1 March 2017 in accordance with the now invalid standard STN 34 1398:2014, or with a national standard adopted by a foreign national standardisation body which does not meet the minimum requirements set out in the valid lightning protection standards, our company will assess the equipment as failing to meet the essential safety requirements for technical equipment under the valid legislation and other regulations on ensuring occupational health and safety.