Earthing of Electrical Equipment Above 1 kV AC

Earthing as a safety system

Earthing of electrical equipment above 1 kV AC is one of the key areas of electrical installation safety. Correct design and subsequent evaluation of the earthing system are essential above all for protecting persons against the dangerous effects of electric current under fault conditions.

Requirements for the design and installation of earthing systems for electrical installations with a nominal voltage above 1 kV AC are laid down in STN EN 50522:2023. It sets out the principles a designer must observe so that persons are protected both in normal operation and under fault conditions.

When assessing project design documentation and the design documentation of technical equipment, and when carrying out official tests, we repeatedly encounter shortcomings in the design of earthing systems for electrical equipment above 1 kV AC. Most often, compliance with the permissible touch voltage requirements is demonstrated incorrectly or incompletely.

Basic input parameters for earthing design

The design of an earthing system for electrical equipment above 1 kV AC must be based in particular on the following parameters:

  • magnitude of the earth fault current,
  • duration of the fault,
  • electrical properties of the soil,
  • method of earthing the neutral point of the supply network.

These parameters fundamentally influence the magnitude of the touch voltage UT and the permissible touch voltage UTP. The parameters of the network to which the equipment will be connected must therefore be known as early as the design stage.

Types of networks

The earthing system design must take into account the method of earthing the neutral point of the supply network, as this directly influences the magnitude and duration of the earth fault current.

The basic types of HV networks according to the method of neutral point earthing are:

  • network with an isolated neutral point – the source neutral point is not connected to earth. Such networks are used mainly in industrial plants to supply end equipment.
  • network with a resonant-earthed neutral point – the source neutral point is earthed through an arc-suppression coil compensating the capacitive component of the network. This type is commonly used in distribution networks.
  • network with a neutral point earthed through a low impedance – the source neutral point is connected to earth so that a sufficiently large earth fault current arises during an earth fault. This type is used mainly in cable distribution networks.

Permissible touch voltage

The permissible touch voltage UTP is the limit value of the touch voltage UT, which depends on the duration of the fault.

The earthing system voltage UE arises as a voltage drop when the current flowing into the earth IE passes through the earthing impedance ZE.

It is not enough to assess the earthing system resistance alone. What is decisive is verifying that the permissible touch voltage UTP will not be exceeded during a fault – a requirement often neglected or incorrectly evaluated in practice.

Particular attention must be paid to 22/0.4 kV transformer stations, where a common earthing system generally serves both the HV and LV parts. Here the earthing system potential can be transferred via the PEN conductor into the low-voltage network towards the customer.

An earthing system resistance of up to 2 Ω at HV/LV transformer stations may not always be sufficient

In practice, we often encounter the assumption that the total earthing system resistance of an HV/LV transformer station should be no more than 2 Ω in accordance with STN 33 2000-4-41. Although commonly used, this value cannot be regarded as generally binding or automatically sufficient in every case.

What is decisive is whether the designed earthing system meets the requirements of STN 33 2000-4-41 as well as STN EN 50522 for the permissible touch voltage under the real fault parameters of the network.

A correct earthing system design must always be based on the specific conditions of the installation concerned.

In other words, merely achieving the maximum earthing resistance of 2 Ω under STN 33 2000-4-41 at HV/LV transformer stations does not in itself mean the earthing system is satisfactory in terms of protecting persons.

Conclusion

When designing and evaluating the earthing of electrical equipment above 1 kV AC, it is crucial to demonstrate that the earthing system will protect persons against dangerous touch voltage during a fault.

The earth fault current magnitude, the fault duration, the method of neutral point earthing and the soil properties are among the decisive input parameters that must be considered in earthing system design.

Particular attention is required for transformer stations with a common HV and LV earthing system, where an earth fault can transfer the earthing system voltage UE to the low-voltage side. In precisely these cases, thorough evaluation of the permissible touch voltage is essential.

A correctly designed and verified earthing system is therefore not only a technical requirement but above all a fundamental prerequisite for the safe operation of electrical equipment.