New Requirements for Inspections of Electrical Appliances (STN 33 1630)

On 1 May 2025, the new national standard STN 33 1630:2025 came into force, governing how inspections and checks of electrical appliances and extension leads are to be carried out during their use.

What does STN 33 1630 change?

This standard is the key standard for unifying the categories (hand-held electrical appliances, electric hand tools, other electrical appliances and extension leads) and for clearly setting the intervals for repeated inspections.

The requirements of the already applicable standards STN EN 50699:2022 and STN EN 50678:2022 have been incorporated into the new national standard STN 33 1630:2025, which merged and replaced the original standards STN 33 1610:2002 and STN 33 1600:1996, thereby removing inconsistencies and aligning the terminology with that currently in force.

An important point is that the publication of the new standard STN 33 1630:2025 introduces a transition period until 1 May 2027, during which checks of electrical appliances may still be carried out in accordance with the original standards, unless other legislation provides otherwise.

Which equipment does STN 33 1630 not apply to?

The standard STN 33 1630:2025 does not apply to:

  • electrical equipment forming part of fixed electrical installations, which is covered by the STN 33 2000 series of standards,
  • uninterruptible power supplies (UPS),
  • photovoltaic inverters and power converters, e.g. AC/DC converters,
  • charging stations for electromobility,
  • stationary power supply sources (generators),
  • programmable logic controllers (PLC),
  • power drives,
  • electrical equipment and devices intended for explosion-hazardous areas or for mining use,
  • cord lines intended for the temporary distribution of electricity at temporary workplaces
  • machinery tested in accordance with STN EN 60204-1,
  • medical electrical devices tested in accordance with STN EN 62353,
  • battery-powered electrical appliances and protection class III equipment as defined in STN EN 61140

Intervals for repeated inspections

The intervals below are set by STN 33 1630:2025 for protection class I and II appliances.

Group by area of useElectric hand tools and hand-held appliancesExtension leads exposed to mechanical stressOther electrical appliances and/or extension leads not exposed to mechanical stress
AAlways before hiring out and, for long-term hire, at the intervals of the relevant group by use (B, C, D, E)
BOnce every 6 monthsOnce every 6 monthsOnce every 6 months
COnce every 6 monthsOnce every 6 monthsOnce every 12 months
DOnce every 6 monthsOnce every 6 monthsOnce every 12 months
EOnce every 12 monthsOnce every 12 monthsOnce every 24 months

A – Appliances and extension leads provided for hire

B – Appliances and extension leads used outdoors, or indoors with the external influence of water AD3 or higher.

C – Appliances and extension leads used in indoor areas

D – Appliances and extension leads used in indoor areas accessible to the public

E – Appliances and extension leads used for administrative and office work.

What is new in day-to-day practice?

First of all, the “table-based” way of thinking is being abandoned in favour of a single, unified test procedure, with the emphasis on verifying the effectiveness of protective measures throughout the equipment’s life cycle.

STN EN 50699:2022 sets out the requirements for carrying out repeated tests of electrical appliances, whether plug-connected devices or permanently connected appliances up to 1 000 V AC/1 500 V DC and up to 63 A.

The aim is not to measure everything “just in case”, but to demonstrate that protection against electric shock is still effective and that the measured values do not exceed the permissible limits.

In practice, this means choosing the right combination of:

  • a visual inspection,
  • a test of the continuity of the protective circuit,
  • measurement of insulation resistance or, where appropriate, leakage currents – depending on the type of equipment and its design.

STN EN 50678:2022 is the second “sister” standard, which sets out the general procedure for verifying the effectiveness of the protective measures of electrical appliances after repair.

After every service intervention, an electrical equipment inspector (or a qualified worker) must once again demonstrate the effectiveness of the basic protective measures.

This eliminates the risk that a well-intentioned repair could impair safety (e.g. by changing the routing of the protective conductor, altering the degree of protection of the enclosure, or through faulty assembly).

Conclusion

The standard STN 33 1630:2025 precisely specifies the categories of equipment according to their use and introduces a separate regime for extension leads. It unifies the intervals for hand tools and hand-held appliances, allowing inspections to be planned more effectively.

Inspections and checks remain part of the prevention system under Act No. 124/2006 Coll. and Decree No. 508/2009 Coll. The new standards provide a technical framework for meeting these statutory obligations in line with modern European practice.

Recommendations for practice:

  • map your equipment portfolio according to the categories set out in STN 33 1630 and assign the correct intervals for repeated inspections,
  • standardise your check and inspection reports – the standard includes a sample report on a check and inspection,
  • add the necessary test instruments and update your test procedures,
  • retrain your staff.

Useful links

Certification of specialists in the field of electrical equipment

STN 33 1630:2025 Inspections and checks of electrical appliances and extension leads during their use (in Slovak)